Water-cool screw chiller unit is widely used in plastics, electronic manufacture, electroplate, pharmaceutical and chemical industry,ultrasonic cooling, printing and other industrial productions. Water-cool screw chiller unit produced by Tianfeng can precisely control the temperature required for modern industrial mechanized production, thus greatly improving the production efficiency and product quality. Water-cool screw chiller unit is easy to operate, designed reasonably and has excellent quality. There are hundreds of its specifications, which is an indispensable companion for modern industrial production.
水冷螺杆式冷水机组也是冷水机的一种,由于它的主要构成部件采用螺杆式压缩机和水冷式冷凝方式,因此得名:水冷螺杆式冷水机组。
水冷螺杆式冷水机组广泛用于塑胶、电子制造、电镀、医药化工、超声波冷却、印刷等工业生产,田枫水冷螺杆式冷水机组精确控制现代工业机械化生产所要求温度,从而大大提高了生产效率及产品质量。水冷螺杆式冷水机组操作简便、设计合理、品质卓越,其规格有上百种,是现代化工业生产不可缺少的良伴。
1.Technical Parameter Shoot(Water-Cool Low Temperature Chiller-15℃ Double-Unit 1)
Model |
TFW- |
||||||||||||
86.2e |
120.2e |
160.2e |
174.2e |
218.2e |
230.2e |
270.2e |
290.2e |
316.2e |
340.2e |
||||
Nominal Refrigeration Capacity |
kW |
86 |
120 |
160 |
174 |
218 |
230 |
270 |
290 |
316 |
340 |
||
104kCal/h |
7.4 |
10 |
14 |
15 |
19 |
20 |
23 |
25 |
27 |
29 |
|||
Operating And Control Mode |
Automatic Control Of PLC Programmable Controller |
||||||||||||
Power Supply |
380V/3N~/50Hz |
||||||||||||
Compressor |
Type |
5-6 Asymmetrical Semi-Enclosed Twin-Screw Compressor |
|||||||||||
Quantity |
2 machine |
||||||||||||
Startup Type |
Y-△ Start-Up |
||||||||||||
Capacity Regulator |
0-16.5-33-50-66-83.5-100% |
0-12.5-25-37.5-50-62.5-75-87.5-100% |
|||||||||||
Input Power |
kW |
43 |
56.6 |
71 |
78 |
96.2 |
103.4 |
104.2 |
122.4 |
134.6 |
147 |
||
Rated Current |
A |
74.8 |
98.5 |
123.5 |
135.7 |
167.4 |
179.9 |
181.3 |
213 |
234.2 |
255.8 |
||
Evaporator |
Type |
High Efficiency Shell And Tube Heat Exchanger |
|||||||||||
Water Field |
m3/h |
18.5 |
25 |
35 |
37.5 |
47.5 |
50 |
57.5 |
62.5 |
67.5 |
72.5 |
||
Pipe Diameter |
|
DN65 |
DN80 |
DN100 |
|||||||||
Water Pressure Drop |
kPa |
49 |
50 |
50 |
50 |
51 |
51 |
51 |
51 |
52 |
53 |
||
Condenser |
Type |
High Efficiency Shell And Tube Dry Heat Exchanger |
|||||||||||
Water Field |
m3/h |
29.3 |
40.1 |
52.5 |
57.3 |
71.4 |
75.7 |
85 |
93.7 |
102.4 |
110.6 |
||
Pipe Diameter |
|
DN65×2 |
DN65×2 |
DN80×2 |
|||||||||
Water Pressure Drop |
kPa |
44 |
45 |
45 |
45 |
45 |
45 |
46 |
46 |
48 |
48 |
||
Overall Dim. |
Long |
mm |
3350 |
3370 |
3370 |
3470 |
3470 |
3500 |
3500 |
3500 |
3600 |
3780 |
|
Width |
mm |
1100 |
1100 |
1100 |
1100 |
1100 |
1300 |
1300 |
1300 |
1300 |
1300 |
||
Height |
mm |
1340 |
1340 |
1340 |
1430 |
1480 |
1660 |
1680 |
1720 |
1775 |
1870 |
||
Unit Weight |
kg |
1340 |
1420 |
1590 |
1970 |
2050 |
2390 |
2570 |
2650 |
2740 |
3420 |
||
Operating Weight |
kg |
1520 |
1620 |
1840 |
2190 |
2360 |
2870 |
3040 |
3080 |
3210 |
3810 |
Remark:
1.The parameters under nominal working condition are as follow:Frozen Water Input/Output Temperature -11℃/-15℃;Cooling Water Input/Output Temperature 30℃/35℃.
2.Temperature Condition:Frozen Water Output Temperature Range -17℃~-7℃, Cooling Water Input Temperature Range 19℃~33℃
3.Refrigerator side should be used 40%(V/V) glycol solution or 24%(m/m) calcium chloride solution as antifreeze.
4.The water side pressure of evaporator and condenser is 1.0mpa.
5.The water side fouling factor of evaporator under nominal working condition is 0.018m2•℃/kW, for condenser is 0.044m2•℃/kW.
6.Except the specifications and requirements above, Shanghai Tianfeng chiller manufacturer can provide non-standard chillers according to customer demands.
注:
1.名义工况中参数如下:冷冻水进/出水温度-11℃/-15℃;冷却水进/出水温度30℃/35℃.
2.温度条件:冷冻水出水温度范围 -17℃~-7℃, 冷却水进水温度范围 19℃~33℃
3.机组冷冻侧须采用40%(V/V)的乙二醇溶液或24%(m/m)的氯化钙溶液作防冻剂;
4.蒸发器和冷凝器的水侧设计承受压力为1.0mpa。
5.名义工况中蒸发器水侧污垢系数为0.018m2•℃/kW,冷凝器水侧污垢系数为0.044m2•℃/kW;
6.除上述规格和要求外,田枫冷水机厂家可根据客户要求提供非标产品。